Power System Decarbonization: Impacts of Energy Storage Duration and Interannual Renewables Variability

Mehdi Jafari, Magnus Korpas, Audun Botterud

arXiv:1911.12331v1eess.SYcs.SY

TL;DR

This paper asks how storage duration and interannual VRE and load variability affect power-system decarbonization planning. It optimizes Italy’s 2050 capacity and operation across multiple years, finding that storage can reduce decarbonization costs while single-year planning can raise costs in other years.

  • Problem

    The study addresses limited exploration of long-duration storage economics and of how annual VRE and load variability affects zero-carbon system configurations and planning costs.

    Source: §1 · p. 2
  • Method

    The authors optimize Italy’s 2050 generation expansion and operation under emissions constraints, examining storage scenarios and single-year versus 11-year VRE and load data.

    Source: §1 · p. 2
  • Results

    Up to 10% year-to-year energy-cost variation occurs, while the zero-emission generation-cost increase falls from 40% without storage to 20% with batteries.

    Source: §5 · p. 10, §6 · p. 11
  • Takeaways & Limitations

    Multi-year capacity-expansion optimization is the best solution in the Italy case study, and storage can lower system costs while longer durations have modest marginal value per kWh.

    Source: §6 · p. 11

    The study’s assumptions and inputs are highly uncertain, particularly over the long horizon to 2050.

    Source: §5 · p. 10

Abstract

from arXiv · show

Decarbonization of the electricity sector is one of the major measures in slowing down the pace of climate change. In this paper, we analyze the impacts of energy storage systems (ESS) and interannual uncertainty of variable renewable energy (VRE) on power system decarbonization in 2050. We perform capacity expansion optimization based on technology cost projections and CO2 emission restrictions using 11 years of VRE and load data in Italy's power system, with a particular focus on the role of ESS and its duration. We also explore capacity expansion optimization based on multiple-year vs. single-year data to quantify the impact of VRE interannual variability. Our results indicate high renewables penetration even in the absence of decarbonization policies. In the transition to zero carbon system, CCS plays a minor role due to its carbon capture efficiency. ESS investments contribute to lower system costs by replacing more expensive flexibility resources. However, longer ESS durations have lower marginal value per added kWh ESS. Interannual variability of VRE substantially changes the system's configuration and energy cost. Decision-making based on single-year data substantially increases the systems' operational costs in other years. In contrast, optimizing over multiple years provides a more robust and cost effective generation expansion strategy.

1. Introduction

The paper examines how storage duration and year-to-year variation in renewables and load affect least-cost power-system decarbonization in Italy by 2050. It addresses open questions about long-duration storage economics and the consequences of planning from a single year of data.

1. Introduction

  • Long-duration storage remains an open economic question: its viability and added system value are unclear.Prior work links storage value to its size, duration, costs, and CO2 constraints.Source: §1 · pp. 1–2
  • Single-year planning can produce suboptimal operation, unserved demand, and higher costs in other years, while VRE and load patterns vary annually.Prior studies show that VRE variation can significantly change system costs, but zero-carbon configurations and the effects on all generation technologies remain less explored.Source: §1 · p. 2
  • The study evaluates Italy’s 2050 least-cost system under different emissions limits, storage options, and 11 years of VRE and load data.It uses integrated investment and operation optimization and compares multi-year planning with decisions based on single-year data.Source: §1 · p. 2
  • The analysis also examines flexibility and low-emission technologies, storage durations up to 100 hours, and uncertainty effects on system configuration, costs, reliability, and operating costs.The authors identify these as the study’s main contributions.Source: §1 · p. 2

2. Methodology

The methodology co-optimizes generation investment and system operation, including operational and emissions constraints. It extends planning across multiple years to represent weather and load uncertainty, while relaxing integrality constraints to reduce computational effort.

2. Methodology

  • GenX is modified to co-optimize generation investment and operation for the 2050 system within one planning model.The optimization includes capacity expansion, hourly unit commitment and dispatch, and reserve scheduling.Source: §2 · p. 2
  • The model imposes technology investment and operating limits, unit commitment and reserve constraints, annual CO2 caps, hourly energy balance, and system reserve requirements.Hourly supply must balance load unless load curtailment occurs; constraints (b)–(g) apply to each year in the stochastic formulation.Source: §2 · p. 3
  • Multi-year planning minimizes expected demand-meeting costs across weather and load years, while single-year investments are also tested against other realized years.The objective incorporates multi-year fixed and variable costs, with weights normalizing costs to an annual value.Source: §2 · p. 3
  • The mixed-integer formulation is relaxed to a linear program to speed computation, an approximation earlier studies found to have limited impact on expansion results.The planning model requires assumptions about generation, load, renewables, storage, technology costs, and fuel prices.Source: §2 · p. 3

3. Input Data and Assumptions

The input assumptions combine historical Italian system data with projections for 2050. They specify technology availability and costs, storage options, load growth, and a simplified system representation.

3. Input Data and Assumptions

  • The study builds on prior Italy analysis that projected renewables could exceed 90% penetration by 2050 but did not account for interannual VRE variability.Current RES generation is reported as 35–40%, with variation related to water availability and hydro generation.Source: §3 · p. 3
  • For 2050, coal and oil expansion are excluded, while CCGT, OCGT, and CCGT with post-combustion CCS are available as thermal options.CCS is assumed to capture 88% of CO2; biofuel generation is treated as carbon-emissions-free, and thermal-unit outages and maintenance downtime are not modeled.Source: 3-1. Generation Units · p. 4
  • Renewable inputs include solar, wind, hydro, geothermal, and bioenergy, with hydro, geothermal, and co-generation bioenergy expansion constrained or fixed.Hydro is limited to about 22 GW and 45 TWh annually; run-of-river hydro has constant hourly availability, and bio electricity-only units are dispatchable and provide reserves.Source: 3-1. Generation Units · pp. 3–4
  • Hourly solar and wind availability uses Renewables Ninja data for 2006–2016, scaled to projected 2050 averages, while technology costs use European Commission projections.A 10% discount rate is used for annuities.Source: 3-1. Generation Units · p. 4
  • Projected 2050 generation requirements are 404 TWh, with 7% transmission and distribution losses and no electricity imports or exports assumed.Transmission network limits are omitted; plants are aggregated, and operating reserves are set as percentages of hourly load and VRE generation.Source: 3-3. Load and System Representation · p. 5

4. Results

The results compare emissions limits and battery options across weather/load years, then examine storage duration and planning under single- versus multiple-year data. They show strong renewable penetration without CO2 constraints, with storage, emissions policy, and interannual variation changing the resulting system mix.

4.1. CO2 Emission Constraints and Battery Installation

  • 80% of installed capacity and 73% of demand are renewable without batteries; with batteries, renewable capacity reaches 91% and annual generation share reaches 85%.Source: §4.1.1 · p. 5, Figure 1 · p. 6, Figure 2 · p. 6
  • Battery cases show greater weather/load variation in generation shares, particularly for wind and bio, than cases without batteries.Without batteries, max–min variation is 13% for gas, 19% for wind, 9% for solar, and 20% for bio; with batteries, it is 20%, 35%, 11%, and 40%, respectively.Source: §4.1.1 · p. 5, Figure 1 · p. 6
  • Tighter CO2 limits shift flexible generation from gas to CCS and then bio; batteries reduce gas and bio generation while favoring solar over wind.Under zero emissions, CCS is unsuitable because its capture efficiency is below 100%.Source: §4.1.1 · pp. 5–6, Figure 1 · p. 6, Figure 2 · p. 6
  • Average curtailment is 4% for solar versus 23% for wind, and tighter CO2 limits increase renewable curtailment.Solar curtailment is higher with batteries and wind curtailment lower; 8-hour battery capacity is 2–5 times that of 3-hour batteries across CO2 constraints.Source: Figure 3 · p. 6, §4.1.1 · p. 6

(TWh)

Batteries lower energy costs, while their value depends on storage duration; weather- and load-year variability can also change system costs and the preferred capacity mix. Comparing single-year planning with an 11-year optimization shows why planning across years can yield more robust outcomes.

  • In the no-limit case, batteries reduce average emissions from 97 g to 54 g per kWh consumed, while emissions still vary 40% across weather and load data.The energy-cost figure compares cost per MWh against CO2 emissions with and without batteries across weather and load data.Source: §4.1.2 · pp. 6–7, Figure 4 · p. 7
  • Almost 20% energy-cost reduction with batteries in the zero-emission system, versus 7% without a CO2 constraint.Without batteries, energy not served can reach 20 GWh and unmet reserves 40–60 GWh; batteries reduce both substantially.Source: Figure 5 · p. 7, §4.1.2 · p. 7
  • At 100-hour duration, ESS breakeven cost reaches 85 USD/kWh; long-duration storage is not critical for this case study.The analysis holds energy capacity constant while changing power to represent duration, and excludes ESS investment costs from the optimized system costs.Source: §4.2 · pp. 7–8, Figure 6 · p. 8
  • Breakeven cost is higher for the first, smaller ESS installations, while uncertainty affects short-duration systems more; at 100 hours, variation stays below 5%.For 3-hour ESS, breakeven-cost deviations are 30%, 20%, and 12% for 1, 10, and 100 GWh, respectively.Source: §4.2 · p. 8, Figure 6 · p. 8
  • Lower-duration storage boosts solar generation, while longer durations shift generation shares back toward the no-ESS mix; at 100 GWh, bio remains lower because ESS supplies flexibility.One- and three-hour ESS particularly increase solar’s contribution by shifting midday generation to evening peak-load hours.Source: §4.2 · p. 8, Figure 7 · p. 8
  • The 11-year optimization minimizes expected costs across all weather and load years, and its zero-emission portfolio is compared with single-year plans.The analysis uses historical hourly patterns from 2006–2016 while scaling annual VRE availability factors to the same 2050 value.Source: §4.3 · pp. 8–9
  • Single-year solutions vary substantially by technology: offshore wind capacity varies up to ±100%, while the 11-year co-optimized solution differs from the single-year average.Annual VRE availability factors are scaled to the same 2050 value; historical years contribute their hourly variation patterns.Source: §4.3 · p. 9, Figure 8 · p. 9
  • Planning from 2009 or 2010 performs worst in other years, whereas 2008, 2015, and the 11-year plan show narrower operating-cost variation.The authors attribute the poor outcomes to mismatch between VRE output and load, causing capacity inadequacy and costly load curtailment.Source: §4.3 · p. 9, Figure 9 · p. 9, Figure 10 · p. 10

5. Discussion

In Italy, energy storage lowers the cost of reaching zero emissions, while its value depends on capacity and duration. Year-to-year VRE and load variability can alter expansion decisions and costs, and the study’s 2050 assumptions are highly uncertain.

5. Discussion

  • Without ESS, the optimal plan tends toward costlier flexibility options such as bioenergy and natural gas with CCS; ESS enables more RES and lowers investment and operating costs.The study does not model social or political limits on resource expansion, or network, transmission, and distribution constraints.Source: §5 · p. 10
  • Full decarbonization without energy storage increases energy generation cost by 40%, versus 20% with batteries, largely because bio-generation provides costly flexibility.The increase in system cost is greater when emissions are cut from 10% to zero than when moving from no limit to 10% emissions.Source: §5 · p. 10
  • ESS benefits decline at higher installed capacity; durations under 24 hours have the greatest configuration and cost impacts, with shorter storage favoring solar and longer storage favoring wind.Durations beyond 100 hours, including seasonal storage, were not analyzed.Source: §5 · p. 10
  • Across 11 years, hourly VRE and load variation changed optimal expansion despite constant average annual capacity factors, and single-year planning could raise costs in other years.The study recommends optimizing across multiple years or using a single-year worst-case scenario for a more robust plan.Source: §5 · p. 10
  • The study’s assumptions and inputs are highly uncertain, particularly given the long horizon to 2050.Source: §5 · p. 10

6. Conclusion

For Italy, renewables reach high penetration even without CO2 constraints, while gas plants with CCS play a minor role. ESS reduces costs under the stated assumptions, and multi-year weather and load data support more robust expansion planning.

6. Conclusion

  • High RES penetration occurs even without a CO2 constraint or economic RES incentives, while gas power plants with CCS play a minor decarbonization role because capture efficiency is below 100%.Source: §6 · p. 10
  • Under the given technology-cost assumptions, ESS lowers system costs and reduces ENS, while storage under 10 hours adds significant value and 10–100-hour storage has modest marginal value per kWh.ESS increases solar curtailment in the optimal mix; first installed capacities deliver greater system-cost savings and higher breakeven cost.Source: §6 · p. 11
  • In the Italy case study, energy costs vary by up to 10% depending on the year optimized, and single-year plans can produce costly, high-curtailment operation in other years.The study concludes that capacity expansion should be optimized across multiple years of weather and load data.Source: §6 · p. 11
  • Future work includes optimizing ESS duration within capacity expansion, modeling degradation, testing broader technology-cost and fuel-price assumptions, and including transmission networks and grid stability.Source: §6 · p. 11