Intelligent Fault and Lightning Detection Algorithm for VSC-MTDC grids based on ResNet with Hybrid Attention Mechanism
Yunqi Zhang
TL;DR
VSC-MTDC grids need accurate, rapid fault and lightning detection, but their changing conditions complicate the task. The paper converts double-ended ICTWs into S-transform images and analyzes them with RWHAM; simulations report high accuracy, rapid detection, and generalization across parameter changes.
Problem
Fault and lightning detection in VSC-MTDC grids must be accurate and rapid to support safe, stable operation as transmission systems scale.
Source: §I · p. 1Method
The method transforms double-ended ICTWs into time-frequency images and uses an RWHAM model with hybrid attention to emphasize key image information.
Source: §I · p. 2Results
The 21,620-case PSCAD/EMTDC evaluation reports 99.97% detection accuracy under nominal grid configurations and above 99.94% with changed parameters; detection is within 5 ms for lines up to 508 km.
Source: §I · p. 2, §VI · p. 10Takeaways & Limitations
The authors report reliable fault and lightning detection that generalizes when VSC-MTDC grid parameters change.
Source: §I · p. 2, §VI · p. 10
Abstract
from arXiv · showhide
To address the existing challenges in fault detection for voltage source converter-based multi-terminal DC (VSC-MTDC) grids, this paper proposes an intelligent fault and lightning detection algorithm based on S transform and Residual Network with hybrid attention mechanism (RWHAM).The DC line double-ended initial current traveling waves (ICTWs) are first converted into time-frequency matrices by performing S transform and then visualized as a two-dimensional image. The image effectively characterizes the time-frequency features of ICTWs under different fault and lightning conditions, making it easier to extract critical features for the models. Next, the RWHAM model is constructed and the images are fed into the model to detect internal and external faults and lightning interference. The weight of the key information in the image is increased by hybrid attention mechanism, which in turn improves the fault detection ability of the RWHAM model. Extensive simulations involving 21,620 distinct cases on PSCAD/EMTDC validate the algorithm's high accuracy and rapid response across different types of faults and lightning interference. Furthermore, it exhibits excellent generalization ability when the parameters of VSC-MTDC grids change.
I. INTRODUCTION
The introduction frames VSC-MTDC fault and lightning detection as requiring accuracy and speed amid increasingly complex grids, and proposes an S-transform/RWHAM approach. It reports validation on 21,620 simulated cases.
- Fault and lightning detection must be accurate and rapid because VSC-MTDC faults can escalate within milliseconds, leaving little transient data before circuit breakers must act.Source: §I · p. 1
- Prior physical-model methods face sensitivity to fault conditions, system parameters, and manually set thresholds, while earlier deep-learning studies did not address internal lightning interference.Source: §I · pp. 1–2
- The proposed method converts double-ended ICTWs into S-transform time-frequency images, then uses RWHAM hybrid attention to emphasize key image information for fault and lightning detection.Source: §I · p. 2
- 21,620 PSCAD/EMTDC test cases support reliable, rapid fault and lightning detection with excellent generalization ability for VSC-MTDC grids.Source: §I · p. 2
II. RESEARCH SYSTEM
The study uses a four-terminal VSC-HVDC system and converts double-ended initial current traveling waves (ICTWs) into time-frequency images. These images expose terminal-pattern differences across internal faults, external events, and lightning interference.
II. RESEARCH SYSTEM
- The test system is a four-terminal bipolar VSC-HVDC grid with two topologies and 100-km frequency-dependent overhead lines.Current-limiting reactors are installed at line terminals or converter-station outlets.Source: §II · pp. 2–3
III. TIME-FREQUENCY FEATURE EXTRACTION USING S-TRANSFORM
- Phase-modal transformation decouples bipolar DC currents before the S-transform is applied to 1-mode current traveling waves at both line terminals.The S-transform provides higher frequency resolution at low frequencies and higher time resolution at high frequencies.Source: §III · p. 3
- A 0.2 ms ICTW window is rendered as a 224×224-pixel, 3-channel image by concatenating the two terminal matrices horizontally.The window avoids subsequent reflected and refracted waves while limiting detection delay; each single-terminal image spans 0–0.2 ms and 0–50 Hz on its time and frequency axes.Source: §III · p. 3
- Internal faults and lightning show similar two-terminal ICTW color trends, unlike external events; frequency patterns also distinguish faults from lightning.The images cover internal PGFs, external PPFs, and lightning interference; the tables show cases with varying locations and fault resistances or lightning positions.Source: §III · pp. 3–4, Table II · p. 4, Table III · p. 4
IV. RWHAM BASED FAULT AND LIGHTNING DETECTION ALGORITHM
The proposed RWHAM approach uses ICTW time-frequency feature maps to identify internal faults, internal lightning interference, and external faults or lightning interference. The paper presents it as a way to extract complex features and support accurate, rapid detection.
- The paper proposes RWHAM to balance protection speed and reliability in MTDC grids.The model is used to classify ICTW time-frequency feature maps.Source: §IV · p. 4
- RWHAM extracts complex ICTW time-frequency characteristics that traditional analytical methods are described as difficult to capture.Source: §IV · p. 4
- The feature maps are used to identify internal faults, internal lightning interference, and external faults or lightning interference accurately and quickly.Source: §IV · p. 4
A. Resnet structure
ResNet learns residual mappings rather than directly learning target mappings, and its residual block is extended with BAM to weight informative channels and spatial regions.
A. Resnet structure
- ResNet learns the residual F(x)=H(x)-x, making deep networks easier to optimize than learning the original mapping directly.A typical residual block has two convolutional layers, each followed by batch normalization and ReLU.Source: A. Resnet structure · p. 5
B. Bottleneck Attention Module
- BAM channel attention pools each channel, compresses and restores channel depth, then assigns higher sigmoid weights to more informative channels.The channel representation is compressed to C/16 before being restored to C.Source: B. Bottleneck Attention Module · p. 5
- BAM spatial attention aggregates channel information and uses a 7×7 convolution to assign higher weights to critical spatial regions.Average- and max-pooled maps are concatenated before the convolution produces spatial weights.Source: B. Bottleneck Attention Module · p. 5
- Combining channel and spatial attention captures important features while suppressing irrelevant ones.The BAM output combines the input feature map with both attention maps.Source: B. Bottleneck Attention Module · p. 5
C. The proposed RWHAM model
RWHAM integrates BAM into ResNet blocks to emphasize informative image regions and channels, then trains the classifier on labeled time-frequency images under varied simulated conditions.
C. The proposed RWHAM model
- BAM within RB_blocks weights salient spatial regions and informative channels, with attention focused on terminal-to-terminal trends and low- versus high-frequency image patterns.The model is described as becoming more sensitive to these image patterns, improving detection accuracy.Source: C. The proposed RWHAM model · pp. 5–6, Figure 4 · p. 5
- RWHAM uses four cascaded residual layers containing 3, 4, 6, and 3 RB_blocks, followed by global average pooling and a fully connected classifier.Channel dimensions expand from 64 to 128, 256, and 512; Bayesian optimization selects hyperparameters using validation accuracy.Source: C. The proposed RWHAM model · p. 6
- Attention maps assign higher weights to high-frequency regions for internal lightning and low-frequency regions for faults, while left-terminal amplitude helps distinguish external from internal faults.The paper attributes the fault-versus-lightning distinction to differences in energy distribution across high and low frequencies.Source: C. The proposed RWHAM model · p. 6
D. The training process
- Training simulations span two topologies, multiple DC and AC fault types, fault locations, resistance ranges, and lightning waveforms.Lightning cases include 1.2/50 μs and 8/20 μs double-exponential waveforms; the simulation frequency is 100 kHz.Source: D. The training process · pp. 6–7
- The classifier uses three labels: internal faults, internal lightning interference, and external faults or lightning interference.External faults and lightning share a class because neither triggers a trip signal, whereas internal faults must be distinguished from internal lightning.Source: D. The training process · p. 7
- Training images are resized and cropped to 224×224 pixels, converted to tensors, normalized by channel, and paired with labels.The stated purposes of normalization include faster convergence and more stable gradient updates.Source: D. The training process · p. 7
- Training minimizes cross-entropy loss with L2 regularization using AdamW at a 0.001 learning rate for 30 epochs.The batch size is 128, and the reported loss after 30 epochs is 2.12×10^-5.Source: D. The training process · p. 7
V. SIMULATION VALIDATION AND ANALYSIS
The study validates its algorithm using a PSCAD/EMTDC VSC-MTDC model and 21,968 simulated fault cases.
V. SIMULATION VALIDATION AND ANALYSIS
- A detailed VSC-MTDC grid model was developed in PSCAD/EMTDC for algorithm validation.The model setup is described as the basis for validating the proposed algorithm.Source: §V · p. 7
- The study simulated 21,968 diverse fault cases described in Section IV to generate training datasets.Source: §V · p. 7
- Time-series simulations and numerical calculations were conducted on a computer with an Intel Core i7-1260P CPU.Source: §V · p. 7
A. Typical test
Across 10 runs, the typical test reports per-label accuracy, precision, recall, and F1-score of at least 99.72%, with accuracy standard deviations below 0.01%. The test evaluates 21,620 cases distinct from the training datasets.
A. Typical test
- 21,620 fault cases distinct from the training datasets were simulated to test performance across different fault and lightning locations and types.Source: A. Typical test · p. 7
- The test set contains 7,600 samples labeled 0, 1,368 labeled 1, and 12,652 labeled 2.The section reports calculating each label’s accuracy, precision, recall, and F1 score, plus accuracy standard deviation and ten-run averages.Source: A. Typical test · pp. 7–8
- At least 99.72% average accuracy, precision, recall, and F1-score was achieved for each label across 10 runs, with accuracy standard deviations below 0.01%.The reported test identifies internal faults, internal lightning, and external faults or lightning across locations and withstands fault resistances up to 1005 Ω.Source: Figure 8 · p. 8
B. Generalization ability
The paper examines generalization across grid conditions, including voltage or power scaling and changes to current-limiting reactors. With reactors set to 50 mH or 500 mH, reported test metrics remain high across 10 runs.
B. Generalization ability
- Under voltage-level or transmitted-power scaling, normalization standardizes the time-frequency images, allowing the trained model to be applied without retraining.The passage describes scaling the signal by a factor k while grid impedance parameters remain constant.Source: B. Generalization ability · p. 8
- For 50 mH and 500 mH reactors, average accuracy, precision, recall, and F1-score are each at least 99.72% across 10 runs.Accuracy standard deviations are below 0.02%.Source: B. Generalization ability · p. 9, Table VIII · p. 9
- The algorithm is reported as nearly unaffected by reactor value and able to identify fault and lightning types across diverse topologies and almost all fault locations.Source: B. Generalization ability · p. 9
C. Detection time
Detection time is decomposed into the ICTW window, signal-transmission delays, and processing margin. The reported line-length boundary is 508 km: within it, detection time meets the stated primary-protection limit; beyond it, the algorithm serves as backup protection.
C. Detection time
- Detection time is defined from fault or lightning occurrence to detection completion and comprises T1, T2, and T3.T1 is the 0.2 ms extracted ICTW window; T3 averages 0.58 ms across test datasets.Source: C. Detection time · p. 9
- The transmission-delay components increase with DC line length, and the traveling-wave delay reaches its maximum when a fault occurs at the line terminal.Source: C. Detection time · p. 9
- For VSC-MTDC grids, when a DC line is no longer than 508 km, the algorithm can be used as main protection; when it exceeds 508 km, it can be used as backup protection.Source: C. Detection time · p. 9
D. Comparison with other algorithms
The comparison reports that the proposed algorithm achieves the highest detection accuracy among the compared methods without manual threshold setting. The conclusion reports 99.97% accuracy under nominal configurations and above 99.94% when grid parameters vary without retraining.
D. Comparison with other algorithms
- For a 100 km DC line, maximum detection time is 2.52 ms; for an 800 km line, it rises to 8.33 ms and the method is suitable as backup protection.Source: D. Comparison with other algorithms · p. 10
- Among the compared algorithms, the proposed method achieves the highest detection accuracy, requires no manual threshold setting, and retains strong generalization when system parameters change.The comparison evaluates algorithms across the original system, an 800 km line, and a 50 mH current-limiting reactance.Source: D. Comparison with other algorithms · pp. 9–10, Table IX · p. 10
VI. CONCLUSION
- 99.97% detection accuracy is reported for nominal grid configurations, while accuracy remains above 99.94% under parameter changes without retraining.Source: §VI · p. 10
- For DC lines no longer than 508 km, detection time is within 5 ms for primary protection; in other scenarios the algorithm serves as backup protection.The conclusion attributes the other scenarios' longer detection times to traveling-wave and signal-propagation delays.Source: §VI · p. 10
APPENDIX A
Appendix A provides hyperparameter tables for core layers in BAM, RB_block, and RWHAM.
APPENDIX A
- Tables A.I and A.II list hyperparameters for the core layers in BAM and RB_block.Source: Appendix A · p. 10
- Table A.III reports RWHAM core-layer input sizes, filter sizes, strides, and output sizes for conv1 and conv2.Source: Appendix A · p. 10