Source-linked AI summary

Distributed Sensing on a 110-kV Overhead-Line Maintenance Operation on an Operational Optical Ground Wire

Konstantinos Alexoudis, Torm Järvelill, Hendrik Johann Kerm, Kaida Kaeval, Florian Azendorf, Vincent Sleiffer, Jasper Müller, Chigo Okonkwo, Tom Bradley

arXiv:2609.18767v1eess.SP

TL;DR

Operational OPGW maintenance has lacked remote mechanical verification, while earlier DAS studies focused on passive events. This paper combines DAS and DTSS during a controlled cable lift on a 110-kV line; DAS captures mechanical events and DTSS measures residual strain at the re-clamped tower.

  • Problem

    No method was available to remotely verify the mechanical outcome of overhead-line maintenance, leaving operators reliant on crew reports.

    Source: Introduction · p. 1
  • Method

    The study combined DAS and DTSS on an operational 110-kV OPGW during a controlled cable-lifting operation.

    Source: Introduction · p. 1, Experimental Setup · p. 2
  • Results

    Up to ∼398 µϵ over a ∼336 m section, DTSS found localized residual strain at the re-clamped tower, while DAS matched chain collisions to phone audio.

    Source: Conclusion · p. 3, Results · p. 3
  • Takeaways & Limitations

    OPGW-based DAS and DTSS can capture overhead-line maintenance operations and serve as a real-time asset-monitoring tool for grid operators.

    Source: Conclusion · p. 3

    Without a pre-maintenance reference, relative BFS variations were interpreted as localized strain, but differential temperature contributions between spans could not be fully excluded.

    Source: Experimental Setup · p. 2

Abstract

from arXiv · show

We demonstrate dual-modal distributed sensing on an operational 110-kV OPGW during crane maintenance. DAS resolves meter-scale lifting events and matches impulsive events to phone audio, while DTSS quantifies post-reclamping residual strain up to $\sim$398 $\mu\epsilon$, enabling maintenance verification and asset monitoring in transmission grids.

Introduction

OPGW fibers can support distributed sensing, but prior work focused on passive events rather than planned maintenance. This study combines DAS and DTSS to characterize a controlled cable-lifting operation on an operational 110-kV line.

Introduction

  • OPGW combines a lightning-shield conductor with embedded communications fibers, and DAS and DTSS can measure dynamic vibration and quasi-static strain along the cable.Operators otherwise relied solely on crew reports to confirm maintenance completion.Source: Introduction · p. 1
  • Prior OPGW and adjacent-fiber DAS studies focused on passive events such as wind, ice loading, faults, intrusions, or electrical discharges.Earlier work also demonstrated vibration reconstruction, ice detection, sag extraction, and mechanical-intrusion classification.Source: Introduction · p. 1
  • The study reports combined DAS and DTSS measurements of a controlled cable lift, resolving its mechanical sequence and detecting localized residual strain at the re-clamped tower.The sequence includes ground contact, crane lift, and re-attachment.Source: Introduction · p. 1

Experimental Setup

The study used the embedded OPGW fiber on the Lihula–Virtsu 110-kV line, with one interrogator collecting DAS throughout a three-hour maintenance operation and DTSS afterward.

Experimental Setup

  • The embedded fiber spanned 33.9 km with ∼8 dB link loss; the monitored line included the maintenance tower near 360 m and a tension tower at 3360 m.A 1650 nm OTDR trace with 100 ns pulses confirmed the link length; the interrogator shared the fiber through a 1550/1650 nm filter.Source: Experimental Setup · p. 2
  • DAS used 100 ns pulses and a 10 m gauge length, sampled at 250 MS/s with ∼0.4 m sample spacing and an 800 Hz pulse repetition frequency.A 15–350 Hz bandpass filter was applied during the three-hour measurement.Source: Experimental Setup · p. 2
  • DTSS was acquired after maintenance at approximately 10 m spatial resolution, using a 10.6–11.0 GHz local-oscillator sweep and 2 MHz frequency resolution.Without a pre-maintenance reference, relative BFS variations were interpreted as localized strain, although differential temperature between spans could not be fully excluded.Source: Experimental Setup · p. 2
  • During planned maintenance, the line was de-energized, isolated, and grounded, and all conductors, including the OPGW, were lowered to the ground.DAS began while the cables rested on the ground and continued through the crane lift, re-attachment, and post-maintenance period.Source: Experimental Setup · p. 2

Results

DAS distinguished the ground-resting OPGW from freely suspended cable during lifting, while phone audio corroborated chain-collision events. Post-maintenance DTSS showed localized residual strain near the re-clamped section.

Results

  • Before lifting, the ground-resting span showed ∼3 nϵ dynamic strain; freely suspended aerial sections showed 22–44 nϵ.The 320–740 m low-variation corridor contracted after lift, with only ∼320–390 m remaining at ∼3 nϵ.Source: Results · pp. 2–3, Figure 2 · p. 2
  • Dynamic-strain features extended from ∼390 m to the tension tower at 3360 m, where the dead-end clamp blocked further propagation.A similar reduction appeared near another tower at ∼3100 m; the underlying coupling mechanism remains subject to further investigation.Source: Results · pp. 2–3
  • Two chain-collision events matched on-site audio and DAS reconstructions, with cross-correlations of ρ = 0.79 and 0.71.Both filtered waveforms had a sharp onset and oscillatory decay at a comparable dominant frequency of ∼65 Hz.Source: Results · p. 3, Figure 3 · p. 3
  • Up to ∼398 µϵ of localized residual strain appeared between 100 and 436 m after maintenance, while the aerial link to Virtsu remained near 0 µϵ.The affected region extends beyond the maintained span toward Lihula, consistent with tension redistribution between adjacent spans.Source: Figure 4 · p. 3, Results · p. 3

Conclusion

DAS captured strain changes during controlled cable lifting, while DTSS measured residual strain after reclamping. Together, the measurements show OPGW’s potential for real-time asset monitoring.

  • Up to ∼398 µϵ of localized residual strain change over a ∼336 m section at the re-clamped tower indicated an altered static tension distribution.Source: Conclusion · p. 3
  • DAS recorded dynamic strain from ∼3 nϵ with the cable on the ground to ∼22-44 nϵ when freely suspended between spans.Source: Conclusion · p. 3
  • Phone-recorded chain collisions matched DAS events, indicating potential for DAS playback as a classification tool.Source: Conclusion · p. 3
  • The measurements demonstrate OPGW’s potential as a real-time asset monitoring tool for grid operators using DAS and DTSS.Source: Conclusion · p. 3
Loading 2609.18767v1…