Where Can a Decision Model Diagnose HVAC Faults? Reasoning Demand, Physical Representation, and Robustness Under Shift

Wooyoung Jung

arXiv:2610.09937v1cs.AI

TL;DR

Building fault diagnosis faces system-specific rules, scarce labeled faults, and questions about whether model probabilities remain reliable as operating conditions change. This study evaluates training-free and supervised models on real-building faults across input forms and condition shifts. Decision models diagnosed faults represented by physical features but missed those needing operating context; under shift they retained accuracy and calibration, though their probabilities needed correction and detection remained weak.

  • Problem

    HVAC fault diagnosis relies on expert-tuned rules or labeled data that operating buildings rarely record, while the reliability of training-free model probabilities under changing conditions remains unresolved.

    Source: §1 · pp. 2–3
  • Method

    The study evaluates models on deliberately imposed faults from four real-building datasets and compares performance across shifted conditions against a supervised model.

    Source: §3.3 · p. 11, §3.7 · p. 19
  • Results

    Decision models diagnosed faults whose evidence physical features carry but missed faults needing operating context, and retained accuracy and calibration under shift while their probabilities still needed correction and detection was weak.

    Source: §6 · p. 37
  • Takeaways & Limitations

    The supported practical division is for code to compute physical features, a training-free model to rank candidate faults with recalibrated probabilities, and an operator to make the final call.

    Source: §6 · p. 37

    The study covers occupied-hour air-side faults in four public datasets and one version of the decision model; possible overlap with model training data may raise language-model scores.

    Source: §5.5 · p. 36

Abstract

from arXiv · show

Artificial intelligence supports building operations in several forms, each with its own barrier. Expert rules must be tuned for every system, supervised models need labeled data that buildings rarely record, and language models return free text that requires human-in-the-loop checking, since their stated confidence is unreliable. A newer kind of pretrained model, here called a decision model, returns a probability for every allowed answer, so one model could serve many decisions without training. This study answers three open questions for fault diagnosis in heating, ventilation, and air-conditioning systems: which decisions such a model can make, what input it needs, and whether its probabilities hold when conditions change. On 128 fault days from four public datasets of real equipment, faults are graded by the reasoning their diagnosis demands, with data given raw, as physical features, or with Brick topology. The decision model Jev, open language models, and a supervised model face nine tests that change season, control configuration, or building. Given physical features, Jev and the larger open model diagnosed faults whose evidence one feature carries, but not faults that need operating context. Under shift they kept their accuracy and calibration, while the supervised model lost 0.33 macro-F1 yet led or tied within a building. Their probabilities still needed correction, and detection was weak. The study maps which faults a decision model can diagnose and from what input, and supports a division of work in which code computes the physics and the model ranks candidate faults for an operator.

1. Introduction

Building fault diagnosis combines burdensome expert-tuned rules and data-hungry classifiers with language models whose free-text answers require checking. The study asks which faults training-free decision models can diagnose, what inputs they need, and whether their probabilities remain trustworthy as conditions change.

1. Introduction

  • Rules require system-specific expert tuning, classifiers need labeled faults that buildings rarely record, and language-model outputs require checking because stated confidence can exceed accuracy.Free-text outputs also need parsing and validation before software can act on them.Source: §1 · p. 2
  • A decision model receives a state and typed questions with fixed answer options, then returns probabilities over those options without task-specific training.The paper identifies Jev as one such model and notes its developer's claim that its probabilities track accuracy.Source: §1 · p. 3
  • Prior fault-diagnosis evaluations leave open which faults training-free models can diagnose, whether probabilities are trustworthy, and how performance changes across seasons or equipment.Fault diagnosis is a demanding test because some faults require physical calculations, and wrong diagnoses can send technicians to the wrong component or leave faults running.Source: §1 · pp. 3–4
  • The study asks which faults models diagnose and how reasoning demands affect accuracy, whether physical features or equipment topology help, and whether accuracy and probabilities hold under shifts.The shifts include season, control configuration, and building.Source: §1 · p. 4
  • The evaluation uses 128 real-equipment fault days, four data representations, training-free models, a rule-based reference, and a supervised model tested under shifts.Accuracy and agreement between stated probabilities and observed accuracy are measured.Source: §1 · p. 4
  • The study contributes a map of diagnosable HVAC faults, needed inputs, and probability trust under changing conditions.Harmonized splits, labels, and reasoning-level assignments are available from the author on request.Source: §1 · p. 5

2. Related work

Prior HVAC fault-diagnosis methods face data, system-specific tuning, and reproducibility constraints, while pretrained models have shown uneven diagnostic ability. The literature also leaves open how input representation affects diagnosis and whether accuracy and probabilities hold under changing operating conditions.

2.1. Fault detection and diagnosis: from rules to learned models

  • Supervised HVAC fault-diagnosis methods can perform well but require labeled faults rarely recorded in operating buildings; an audit found nearly all 65 studies irreproducible.Unsupervised methods can flag departures from normal behavior but still need rules, models, or experts to name faults.Source: §2.1 · p. 5

2.2. Pretrained models for diagnosis

  • Training-free language models name some HVAC faults but remain weaker than fine-tuned or supervised systems, and no prior study had evaluated decision models on fault diagnosis.Prior work also reports that LLM performance varies with data presentation, while fine-tuned results depend on labeled faults.Source: §2.2 · p. 6
  • Earlier studies examine individual grounding approaches, but none compare raw data, computed features, and topology across model types under a common protocol.Examples include Brick-graph evidence and workflows combining metadata, causal graphs, and precomputed statistics.Source: §2.2 · pp. 6–7

2.3. Robustness and trust

  • Season, control sequences, and building-specific equipment can change fault appearances, but prior robustness approaches start from trained models and training-free robustness remained unmeasured.The literature also identifies calibration as necessary for probabilities to support alarm thresholds or maintenance ranking, with model confidence sometimes misaligned with accuracy.Source: §2.3 · pp. 7–8

3. Methodology

The methodology evaluates training-free diagnosis across fault reasoning levels and input representations, then tests robustness across shifts in season, control configuration, and building. It uses deliberately imposed faults from four real-building datasets and prespecified observability and reasoning-level assignments.

3.1. Study design

  • Two evaluations address capability and representation across fault days, and robustness across held-out seasons, control configurations, or buildings against a supervised model.The shift evaluation measures changes in accuracy and probability quality.Source: §3.1 · p. 8

3.2. Diagnostic task and reasoning levels

  • Each 60-minute window is classified among normal and recorded fault types; diagnosis uses the most probable class, while fault presence is a separate yes-or-no question.The study grades faults from direct evidence through physical consistency, operating context, and temporal patterns to unobservable cases.Source: §3.2 · pp. 8, 10
  • The reasoning levels correspond to increasingly complex evidence: direct comparisons, physical relations, conditional operating context, and temporal behavior; unobservable faults leave no measured trace.The framework ties these levels to operations on numbers and places each fault at the lowest level whose evidence isolates it in the recorded dataset.Source: §3.2 · pp. 10–11

3.3. Data

  • All four datasets contain deliberately imposed faults on real equipment, spanning three controlled research buildings and one occupied university building.Simulated data are excluded; datasets include seasonal repeats, control-mode changes, and overlapping faults across laboratory and occupied settings.Source: §3.3 · pp. 11–12
  • Data were mapped to Brick point classes and common roles, then restricted to occupied-hour 60-minute windows at a 15-minute stride.Temperatures and control signals were harmonized to common units and scales for model inputs.Source: §3.3 · p. 13
  • Reasoning levels were assigned before model runs from fault physics and available points; among 128 fault days, 5 were L1, 66 L2, 52 L3, and 5 L4.Some imposed faults leave no trace under particular operating conditions, so observability was flagged in advance and unobservable days were analyzed separately.Source: §3.3 · p. 13, Table 3 · p. 14

3.4. Representations

The study compares four input representations and four model types, then evaluates their diagnosis, robustness, and probability quality under controlled shifts. Its protocol fixes model questions and measures performance with per-day, ranking, detection, and calibration metrics.

3.4. Representations

  • R1 encodes 53 code-computed physical features; R1b converts them to fixed named levels, while R2 adds Brick topology and latest point values.R0 instead supplies five-minute raw readings; unsupported features are omitted.Source: §3.4 · pp. 14–15

3.5. Models

  • Jev and Qwen2.5 at 7B and 72B run without training, while LightGBM learns from labeled source data and APAR supplies a rule-based reference.LightGBM settings were fixed partly to avoid tuning on validation windows that could reward memorizing day-specific conditions; its R2 scores equal R1 because topology encoding is fixed per unit.Source: §3.5 · pp. 15–16

3.6. Questions, probabilities, and protocol

  • Every window receives three fixed questions; Jev returns probabilities for each option, while language-model probabilities are rescaled over answer labels and fault probability is elicited separately.For LightGBM, fault probability is one minus the probability of normal; question wording was fixed before scored calls.Source: §3.6 · pp. 16–17

3.7. Evaluations

  • The capability map scores training-free models on fault and fault-free days, while shift tests hold out season, control configuration, or building and compare identical windows across models.LightGBM trains on early portions of occupied source days; its in-domain reference uses later windows from those days, so that reference is optimistic by design.Source: §3.7 · pp. 18–19

3.8. Metrics and statistics

  • Performance is assessed with detection F1, macro-F1, top-3 accuracy, mean reciprocal rank, and calibration measures; day-level resampling supplies 95% confidence intervals.The reasoning-level trend is the Spearman correlation between reasoning level and per-day accuracy, and feature representations are compared by the change in that correlation.Source: §3.8 · pp. 19–20

4. Results

Across nine shift tests, Jev’s macro-F1 stayed stable while LightGBM lost accuracy; within-building comparisons still favored or matched LightGBM. The capability, detection, calibration, severity, and unobservable-fault results qualify that robustness.

4.1. Capability map

  • With physical features, Qwen2.5 72B named 46% of consistency-fault windows correctly versus Jev’s 37%, while Jev led on temporal faults, 72% versus 32%, and alone named direct faults.Both models were weak on context faults at 9% pooled; on ORNL, Jev named context faults on only 10–13% of windows, below the 25% chance level.Source: §4.1 · pp. 20–22, Figure 2 · p. 21

4.2. Detection and false alarms

  • With physical features, Jev’s yes-or-no answer flagged 75–99% of fault windows and 57–94% of fault-free windows; pooled across four datasets, the condition-answer probability flagged 31% of fault-free windows while detecting 65% of fault windows.Source: §4.2 · p. 23

4.3. Robustness under shift

  • LightGBM’s macro-F1 with physical features fell from 0.75 in domain to 0.42 under shift, a loss of 0.33 (95% CI 0.28–0.42); Jev’s average loss was 0.00 with features and 0.01 with topology.Jev’s loss interval included zero, but LightGBM remained ahead in every held-out season on ORNL; training-free models were comparable to LightGBM on RP-1312 and FLEXLAB.Source: §4.3 · pp. 25–26, Figure 3 · p. 26
  • Physical features raised Jev’s average shifted score from 0.21 with raw readings to 0.33, and topology raised it to 0.37; topology helped on RP-1312 but lowered the FLEXLAB score.Option reordering changed open-model macro-F1 by 0.03 on average when reversed and 0.03–0.05 when shuffled; Jev’s changes across tested input variants were generally small.Source: §4.3 · pp. 27–28

4.4. Calibration and recalibration

  • On shifted sets, Jev’s ECE was 0.27 with physical features and 0.28 with topology; source-fitted temperature scaling lowered topology ECE to 0.17, though calibration could overshoot or worsen on some folds.LightGBM’s ECE rose by 0.25 under shift, while no training-free model’s change was distinguishable from zero.Source: §4.4 · pp. 28–30, Figure 4 · p. 29

4.5. Severity

  • Predicted severity correlated weakly with assigned severity across fault days, and within-fault intensity tracked clearly only for the ORNL stuck damper and two additional fault types for the 72B.Severity answers also rarely said “none” on fault-free windows, so they added little to diagnosis.Source: §4.5 · p. 30

4.6. Unobservable faults

  • With physical features, Jev answered “normal” on 88% of unobservable fault windows, compared with 49% of observable fault windows, and named the imposed fault on 2%.Jev and Qwen2.5 72B did not lower confidence on unobservable windows; whether a fault could show had to be judged from operating conditions outside the model.Source: §4.6 · pp. 30–31

4.7. Cost, response time, and repeatability

  • The 190,582 Jev requests cost US$18.69 total, and asking three questions of one unit every 15 minutes would cost about US$3.40 per year.Three ORNL winter passes returned the same most probable answer on 97–99% of windows for Jev, with macro-F1 variation at most 0.011.Source: §4.7 · p. 31

5. Discussion

The discussion finds that training-free models diagnose faults when physical features carry the evidence, but struggle with faults requiring operating context. Their accuracy and calibration held under tested shifts, although their probabilities needed correction and their detection remained too weak for alarms.

5.1. What a training-free model can diagnose

  • With physical features, Jev and Qwen2.5 72B diagnosed faults carried by one feature, but failed when evidence required operating context or was absent from the input.The models performed no better than always answering “normal” on ORNL context-only windows; topology supplied fan speed needed for return-fan faults.Source: §5.1 · p. 33
  • Fault-description wording and input choices affected results; paraphrasing descriptions raised ORNL winter context-fault accuracy, while removing mixing features raised Jev’s RP-1312 spring consistency-fault accuracy from 13% to 43%.The 72B model differed from Jev by fault level, and the 7B model diagnosed almost nothing; the reasoning-level ordering is based on three fault types and is not established generally.Source: §5.1 · pp. 33–34

5.2. Accuracy when conditions change

  • Within-building, LightGBM led or matched training-free models, while training-free models retained accuracy when the building changed.The cross-building reversal rests on only two fault days without the logged-command days, and the within-building comparison used same-unit labeled faults.Source: §5.2 · pp. 34–35

5.3. Trusting the probabilities

  • Jev’s probabilities still differed from accuracy by about 0.27 on shifted sets, but source-fitted rescaling carried over to most tested shifts; LightGBM’s calibration drifted.Rescaling brought Jev and the 72B below LightGBM in calibration error, although it made Jev underconfident.Source: §5.3 · p. 35

5.4. Implications for practice

  • For units without labeled fault histories, the proposed workflow computes physical features in code, ranks candidate faults with a training-free model, and leaves review to an operator.Context-dependent faults should remain with system-specific rules or an engineer; the authors say detection is too weak for automatic alarms.Source: §5.4 · p. 36

5.5. Limitations

  • The evaluation covers occupied-hour air-side faults in four public datasets and one decision-model version; possible training-data overlap and the absence of a same-feature rule-tree baseline constrain interpretation.The study also leaves energy and comfort costs of missed or false alarms for future work.Source: §5.5 · p. 36
  • Answer-set size is confounded with equipment and fault types, and the in-domain reference set differs from the whole-day shifted set in hours represented.Fault levels were assigned by one person; direct and temporal levels each cover five days, all from RP-1312.Source: §5.5 · pp. 36–37
  • Request wording and ordering affect outputs: paraphrasing moved context-fault accuracy by up to 30 points, while answer-option order shifted open-model scores by 0.03–0.05.These effects are small beside LightGBM’s shift loss but matter when comparing training-free models.Source: §5.5 · p. 37

6. Conclusion

The conclusion states that training-free decision models diagnose HVAC faults when code-computed physical features carry the evidence, but their probabilities require recalibration and cannot support alarms. It proposes a workflow in which the model ranks candidates for operator review and identifies extensions for further testing.

6. Conclusion

  • Training-free decision models diagnosed faults whose evidence was carried by physical features, but missed faults requiring operating context and could not drive alarms.The study found accuracy and calibration held under tested shifts, while the model started below the supervised model and did not surpass it within buildings with labeled faults.Source: §6 · p. 37
  • The proposed practice workflow computes physical features in code, ranks candidate faults with recalibrated probabilities, and leaves the final call to an operator.The conclusion names more building pairs, separately logged commands and actuator positions, a same-feature rule-tree baseline, and error-cost estimates as extensions.Source: §6 · pp. 37–38
  • The harmonized splits, labels, and reasoning-level assignments are available from the author on request.The conclusion offers these materials to support further work.Source: §6 · p. 38

CRediT authorship contribution statement

Wooyoung Jung is credited across the study’s conceptualization, methods, software, analysis, investigation, data curation, visualization, and writing.

CRediT authorship contribution statement

  • Wooyoung Jung is credited with conceptualization, methodology, software, formal analysis, investigation, data curation, visualization, and writing.The contribution statement includes both the original draft and review and editing.Source: CRediT authorship contribution statement · p. 38

Declaration of competing interest

The author declares no competing financial interests or personal relationships that could have influenced the reported work.

Declaration of competing interest

  • The author declares no competing financial interests or personal relationships that could have influenced the work.The author states no relationship with TypeSafe AI or Alibaba and says Jev use was paid personally.Source: Declaration of competing interest · p. 38

Funding

The research received no specific grant funding.

Funding

Data availability

The study uses four public datasets, and derived splits and annotations are available from the author on reasonable request.

Data availability

  • All four datasets are public, and the study’s splits, window labels, observability flags, reasoning levels, and severity assignments are available from the author on reasonable request.Source: Data availability · p. 38

Appendix A. Fault types, reasoning levels, and observability

Appendix A maps fault types to reasoning levels, recorded-point evidence, and observability conditions, with levels fixed before model evaluation.

Appendix A. Fault types, reasoning levels, and observability

  • Table A.1 maps each fault to a reasoning level, recorded-point evidence, and observability condition; levels were fixed before modeling, and a window is observable when a condition holds for at least 15 of 60 minutes.Source: Appendix A · p. 39, Table A.1 · p. 39
  • The L1 return-fan failure is indicated by status and power dropping to zero, while its speed command may remain constant.Source: Appendix A · p. 39
  • L2 evidence includes supply-air warming when a heating valve opens, air warming across a closed heating coil, and damper or coil behavior that departs from its command.Source: Appendix A · p. 39
  • L3 faults require evidence such as excess fan pressure for delivered flow, short heating at a given valve position, or incorrect economizer decisions near changeover.Source: Appendix A · p. 40
  • Unstable control is L4, with valve, damper, or fan oscillation over time as its evidence.Source: Appendix A · p. 40

Appendix B. Feature library

Appendix B defines a 53-feature, 60-minute physical representation, with fixed thresholds and a single source-domain fitted quantity.

Appendix B. Feature library

  • The R1 representation computes 53 features over each 60-minute window; unsupported features are omitted from model payloads and retained as missing values for LightGBM.Source: Appendix B · p. 40, Table B.2 · p. 41
  • All feature thresholds were set before modeling, while the fault-free power–outdoor-temperature relation is fitted only on source-domain fault-free windows.Source: Appendix B · p. 41, Table B.1 · p. 41
  • Outdoor-air fraction features can indicate damper mismatch but become uninformative when outdoor and return temperatures are similar; the library has no direct return-fan evidence.Source: Appendix B · pp. 41–42
  • The feature library summarizes coil temperature changes and valve commands, air temperatures, fan and pressure behavior, operating modes, APAR flags, and control stability.Source: Appendix B · pp. 42–43
  • The library also includes power residuals against a baseline fitted on source fault-free data, zone temperature and setpoint excursions, and compressor-use measures.Source: Appendix B · pp. 43–44

Appendix C. Question wording

Appendix C specifies the information and answer choices supplied for HVAC fault diagnosis. Prompts pair each window representation with unit design intent and answer-class descriptions, while requiring a single label without explanation.

Appendix C. Question wording

  • Each request pairs a unit description and design intent with one window representation and three answer choices; language models must answer with exactly one label token and no explanation.Table C.1 supplies the one-word labels and descriptions shown for each answer class.Source: Appendix C · p. 44, Table C.1 · p. 45
  • The unit descriptions specify equipment, operating modes, setpoints, and economizer logic, with examples spanning an RTU and AHUs in research and commercial buildings.The descriptions also direct models to use physical evidence rather than how often a condition occurs.Source: Appendix C · pp. 44–45
  • Answer classes describe observable fault signatures, including damper faults visible only under certain conditions and sensor bias that can leave the reported supply-air temperature on target.For example, an economizer setpoint change is visible only when outdoor air falls in the affected temperature band; a biased sensor can shift true supply air while its reported value appears on target.Source: Appendix C · p. 46
  • The appendix illustrates three input forms for one hour-long fault window: raw readings, physical features, and physical features augmented with Brick topology.The example is a stuck cooling-valve window on AHU-A, selected in advance from the shifted RP-1312 summer test.Source: Appendix C · pp. 48–49
  • In a fixed RP-1312 summer test window, Jev ranked the stuck cooling valve first with raw readings (0.51), but ranked normal first with physical features (0.39) and features plus topology (0.45).With the latter two inputs, the stuck valve was not among Jev’s three most probable answers; the window had been selected by a fixed rule before any answer was read.Source: Appendix C · p. 49

Appendix D. Scores under shift

Appendix D provides per-test diagnosis and calibration results under shift. Its tables define the score comparisons and calibration views, but the supplied passages do not report their values.

Appendix D. Scores under shift

  • Table D.1 supplies the in-domain and shifted scores underlying Figure 3, while Table D.2 gives per-test calibration errors behind the pooled values in Section 4.4.The supplied passages identify the tables’ scope but do not provide their scores.Source: Appendix D · p. 49
  • Table D.1 reports macro-F1 for in-domain reference windows and shifted test sets, with LightGBM receiving the same R1 and R2 inputs.Its shifts include held-out seasons, FLEXLAB VAV-to-CAV control changes, and transfer from RP-1312 to Nesbitt AHU-2.Source: Table D.1 · p. 50
  • Table D.2 reports shifted-test calibration error (ECE) both as stated and after recalibration fitted on in-domain windows.It also gives pooled values across all windows of the nine tests.Source: Table D.2 · p. 50