Grid-Forming AC/DC Converters for Meshed DC Networks via Dual-Measurement Frequency Droop
Hisham Mahmood, Marcelo A. Elizondo
TL;DR
Weak-grid conditions challenge grid-following control, while conventional DC droop does not provide AC-side grid formation. This paper analyzes a dual-measurement frequency droop for meshed MVDC networks. In simulations, it maintains stable operation in islanding and weak-tie fault tests where the grid-following baseline loses stability.
Problem
Grid-following control is sensitive at low short-circuit strength, while conventional DC-voltage/power droop does not provide local AC-side formation at the interfaces.
Source: §I · p. 1Method
The DMFD forms each terminal’s frequency command from local DC-voltage deviation and a filtered DC-port current or power deviation, and the paper analyzes its network steady state and dynamics.
Source: §I · p. 2, §II · p. 2Results
DMFD maintains stable operation through single-terminal islanding and a weak-tie fault, while the GFL baseline loses stability in both tests.
Source: §V · pp. 8–9Takeaways & Limitations
AC synchronization under DMFD closes an effective DC droop, so the meshed network has a well-defined operating point without direct DC-voltage regulation at a terminal.
Source: §VI · p. 9
Abstract
from arXiv · showhide
This paper proposes and analyzes a dual-measurement frequency-droop (DMFD) controller for meshed MVDC networks. Using only two local DC measurements, bus-voltage deviation and a filtered DC-port current or power deviation, the controller enables grid-forming operation at both AC and DC ports across the mesh. Although the DMFD regulates neither the DC voltage nor the DC current directly and acts only on the terminal frequency, it is shown that AC-side synchronization closes an effective DC droop at every synchronized terminal, so that the steady operating point of the mesh exists and is unique. Constant frequency deviations at a terminal and single-terminal islanding enter the same DC equations as equivalent current offsets, with the island frequency fixed by the island power balance, allowing node voltages and branch currents to be obtained from one linear system. The steady-state model yields design-use envelopes to map the droop ratios and the net DC-injection levels into bounds on DC-voltage deviation and terminal currents. A small-signal dynamic model is developed and used to generate eigenvalue loci and damping-ratio charts that guide controller-gain selection. Averaged EMT simulations on a four-terminal ring corroborate the analysis: in regimes where PLL-based grid-following control is known to lose damping, the DMFD controller maintains stable operation and follows the predicted steady-state characteristics.
I. INTRODUCTION
Grid-following controls can be vulnerable at weak AC interfaces, while conventional DC droop does not provide AC-side formation. This paper studies a dual-measurement frequency droop that coordinates grid-forming behavior across meshed MVDC terminals.
II. PROPOSED CONTROLLER
- Each terminal forms its frequency command from local DC-voltage deviation and filtered DC-port current deviation, using only these two DC measurements.At steady state, the filtered current deviation equals the unfiltered deviation.Source: §I · p. 2, §II · p. 2
- The frequency command is integrated into the converter voltage angle without a PLL, and a supplementary local loop limits sustained bidirectional active-power exchange.The steady-state and small-signal models assume the power-limit loop is unsaturated.Source: §I · p. 2, §II · p. 3
I. INTRODUCTION
- AC synchronization under DMFD closes an effective DC droop, giving a connected mesh a unique operating point without direct DC-voltage or current regulation.The paper states that this preserves the validity of conventional MTDC DC-side models.Source: §I · p. 2
- A terminal frequency bias and single-terminal islanding enter the DC nodal equations as equivalent current offsets, with island frequency set by local power balance.The resulting effects on node voltages and branch currents are computable from the linear equations.Source: §I · p. 2
- Design envelopes relate droop ratios and net DC injections to voltage bands and current limits, while small-signal damping maps guide gain selection.Voltage-only droop is marginally stable with an undamped oscillatory mode; the DMFD current channel damps it.Source: §I · p. 2
II. PROPOSED CONTROLLER
- The current-based DMFD keeps steady-state network equations linear in network variables, unlike the power-based form, which introduces operating-point values into those equations.Both forms yield identical DC-network matrices.Source: §II · pp. 2–3
III. STEADY-STATE MODEL
The steady-state model represents the meshed DC system using a node–branch network and derives its operating point under current-based DMFD. It then specializes the analysis to frequency bias and single-terminal islanding and uses the resulting maps to form design envelopes.
III. STEADY-STATE MODEL
- The steady-state section derives and proves uniqueness of the operating point, then treats a terminal frequency bias and single-terminal islanding before constructing four-terminal-ring design envelopes.The section description identifies the analysis scope; the network equations use a standard node–branch representation.Source: §III · p. 3, A. Network Model · p. 4
A. Network Model
- The node–branch model defines oriented branches, incidence matrix, resistances, inductances, node capacitances, node voltages, branch currents, and converter and exogenous injections.Converter currents and exogenous injections are positive into the DC grid.Source: A. Network Model · pp. 3–4
- At steady state, Kirchhoff’s current law and Ohm’s law yield the network relations, with L_R denoting the resistive Laplacian of the DC mesh.The passage identifies the network laws and names the resulting resistive mesh matrix.Source: A. Network Model · p. 4
B. DMFD Steady-State Relation and Effective Droop
The steady-state model converts the current-based DMFD law into a physical DC-current relation, with per-unit controller gains mapped into effective SI droop matrices. This provides a common network representation for terminals with different ratings.
- The formulation defines scheduled DC current as positive into the grid and uses positive voltage and current droop gains for each terminal.The controller relation is expressed using terminal-specific per-unit metering and gains.Source: B. DMFD Steady-State Relation and… · p. 4
- At steady state, with converter limits inactive and zero power-limit bias, the filtered current equals the measured current.Source: B. DMFD Steady-State Relation and… · p. 4
- Solving the steady-state relation gives the physical converter current as a function of the scheduled current and DC-voltage deviation.Source: B. DMFD Steady-State Relation and… · p. 4
- The controller enters the network model through effective SI droop matrices, allowing terminals with different ratings to share one physical network model.The network matrices remain in SI units while controller gains are tuned locally in per unit.Source: B. DMFD Steady-State Relation and… · p. 4
C. Operating Point, Existence, and Uniqueness
AC synchronization fixes terminal frequency, which closes an effective DC droop without direct DC-side regulation. Under the stated network and gain conditions, this yields a unique operating point for specified injections and frequencies.
- For an unsaturated, connected DC network with positive line resistances and positive effective droop coefficients, the steady operating-point matrix is invertible.The uniqueness argument uses nonnegative line and droop terms; connectivity and positive droop force the homogeneous voltage solution to zero.Source: C. Operating Point, Existence, and… · p. 4
- AC synchronization fixes terminal frequencies, creating effective DC droop even though the controller acts only on terminal frequency.Source: C. Operating Point, Existence, and… · p. 4
- Each specified frequency vector determines a unique DC-network solution for fixed scheduled converter currents and exogenous injections.The solution determines DC-voltage deviations and branch currents, with converter currents following from the controller relation.Source: C. Operating Point, Existence, and… · p. 4
- When scheduled converter currents do not balance exogenous injections, droop corrections absorb the mismatch and produce DC-voltage deviations.Source: C. Operating Point, Existence, and… · p. 4
- The actual operating-point values can differ from nominal voltage and scheduled current.Source: C. Operating Point, Existence, and… · pp. 4–5
D. Frequency Bias and Islanding
A steady frequency bias at one synchronized terminal enters the DC equations as an equivalent current offset. For an islanded terminal, island power balance determines its frequency, and the resulting DC voltages and currents follow from the same network model.
1) Single-Terminal Grid-Frequency Bias:
- A single terminal's prescribed frequency deviation enters as an equivalent nodal-current offset, shifting DC voltage and converter and branch currents.The voltage shift is relative to the nominal-frequency operating point.Source: 1) Single-Terminal Grid-Frequency Bias · p. 5
2) Islanded Terminal:
- For an islanded terminal, island power balance determines its otherwise-unprescribed frequency, with the other terminals held at nominal frequency.The island demand is specified as frequency-independent, and converter losses are neglected.Source: 2) Islanded Terminal · p. 5
- The islanded-terminal equations are linearized around the nominal-frequency operating point before deriving the frequency–power map.Source: 2) Islanded Terminal · p. 5
- A unique islanded operating point additionally requires nonzero steady frequency-to-power sensitivity at the islanded terminal.For the positive gains considered, this condition is satisfied; the resulting DC voltages and currents follow from the network equations.Source: 2) Islanded Terminal · p. 5
E. Design Envelopes for a Four-Terminal Ring
The design envelopes relate DC-voltage deviations to disturbance patterns and amplitude under uniform droop, with a ±0.05 pu admissible voltage band.
E. Design Envelopes for a Four-Terminal Ring
- Disturbances and schedules are represented by a per-unit pattern vector D, scaled by amplitude α and mapped to amperes.Source: E. Design Envelopes for a… · p. 5
- The admissible DC-voltage band is ±0.05 pu, and the droop is uniform unless otherwise stated.Imax denotes the largest per-unit disturbance amplitude considered.Source: E. Design Envelopes for a… · p. 5
- Figure 3 plots node-wise DC-voltage deviation against disturbance amplitude for four patterns at nominal frequency and uniform droop.Dashed lines mark the ±0.05 pu band.Source: Figure 3 · p. 6
- Figure 4a gives the operating-band compliance envelope for uniform droop, while Figure 4b plots worst-case converter current against single-terminal frequency bias.Source: Figure 4 · p. 6
1) Nominal Frequency (∆ω = 0):
The section presents steady-state voltage and current envelopes for nominal operation, frequency bias, and single-terminal islanding, then introduces the dynamic-model scope.
1) Nominal Frequency (∆ω = 0):
- At nominal frequency, node-wise voltage deviations follow near-linear slopes across the canonical disturbance patterns, and the ±Υ band identifies each pattern’s limiting node.The induced ℓ∞ bound defines a safe operating region in the (ρ, Imax) plane.Source: 1) Nominal Frequency (∆ω = 0) · p. 6
2) Single-Terminal Frequency Bias:
- Under a steady frequency bias at one terminal, the worst-case per-unit DC-current magnitude grows linearly with |∆ω|.Source: 2) Single-Terminal Frequency Bias · p. 6
3) Single-Terminal Island:
- For islanded Terminal 2, the island frequency varies with island power change, while the resulting maximum DC-voltage excursion is compared with the ±Υ band.Source: 3) Single-Terminal Island · p. 6, Figure 5 · p. 6
IV. DC NETWORK DYNAMIC MODEL WITH CURRENT-BASED DMFD CONTROL
- The dynamic model couples the DC network, DMFD, and AC active-power dynamics with references fixed and limiting loops inactive.It is intended for gain selection and network-coupled modes at the synchronized grid-connected operating point, not large-signal fault or islanding transients.Source: §IV · p. 6
A. DC-Grid Dynamic Equations
- The DC-grid dynamic equations are introduced using the network orientation defined earlier.Source: A. DC-Grid Dynamic Equations · p. 6
B. Operating Point and Small-Signal Deviations
The model defines operating-point perturbations, then formulates the current-based DMFD and linearized AC active-power channel.
B. Operating Point and Small-Signal Deviations
- The operating point satisfies the steady network and controller equations, and tildes denote perturbations from that point.The voltage and current perturbations are defined relative to their operating-point values.Source: B. Operating Point and Small-Signal… · p. 6
C. Current-Based DMFD and Current Metering
- For a fixed current schedule, the filtered-error perturbation is introduced, and the DMFD relation is expressed in terms of frequency perturbations.Source: C. Current-Based DMFD and Current… · p. 6
D. AC-Side Active-Power Map and Linearization
- The AC active-power channel is represented by a lossless power-angle model and linearized about the operating point.With AC-voltage magnitudes fixed, the first two terms of the expansion are eliminated; a local grid held at operating frequency has eωg,k = 0.Source: D. AC-Side Active-Power Map and… · p. 7
E. DC-Port Power Identity and Current Deviation
The model links DC-port power and current deviations, stacks the resulting dynamics in state-space form, and analyzes dominant-mode behavior across gain sweeps.
E. DC-Port Power Identity and Current Deviation
- With lossless converter coupling, DC-port power satisfies Pdc,k = −Pac,k, and its linearization yields the current-deviation relation.Source: E. DC-Port Power Identity and Current… · p. 7
F. State-Space Stacking
- The state vector stacks voltage, branch-current, active-power, and filtered-current perturbations into a linear system ˙x = Ax + Buu.The third-row blocks follow from the stated DC-port and DMFD relations.Source: F. State-Space Stacking · p. 7
- Figure 6 plots dominant eigenvalue loci while sweeping mdc or mi, and Figure 7 maps the dominant oscillatory-mode damping ratio over the (mdc, mi) gain plane.Source: Figure 6 · p. 7, Figure 7 · p. 7
G. Small-Signal Dynamic Analysis Results
The small-signal analysis finds stable baseline operation and shows that current feedback contributes damping, while the four-terminal-ring EMT simulations support the predicted steady-state behavior across loading, scheduling, islanding, and weak-tie faults.
G. Small-Signal Dynamic Analysis Results
- At the baseline point, the linearized system is stable, with a dominant oscillatory-mode damping ratio of ζdom = 0.71.The dominant-mode damping ratio varies across the (mdc, mi) gain plane; removing current feedback leaves an undamped mode at mi = 0, while positive mi in the evaluated range moves it into the left-half plane.Source: G. Small-Signal Dynamic Analysis Results · p. 7, Power-limit controller · p. 8
V. SIMULATION RESULTS AND DISCUSSION
- An averaged EMT model of the proposed DMFD control was implemented in MATLAB/Simulink for a four-terminal meshed DC network; Table I lists key electrical parameters and controller gains.Table I is labeled “4-terminal ring: baseline values and symbols”; listed values include line resistances [0.75, 0.6, 0.9, 1.5] Ω, inductances [4, 6.36, 4.77, 7.96] mH, and 15 mF node capacitors.Source: §V · p. 8, Table I · p. 8, DC network (4-terminal ring) · p. 8
- Loading ramps keep all node voltages within the ±Υ band, and DMFD and GFL reach essentially identical steady-state operating points.Terminal-3 DC voltage settles at 0.9563 pu with DMFD and 0.9558 pu with GFL.Source: §V · p. 8, Figure 8 · p. 9
- DMFD and GFL follow the scheduled Terminal-1-to-Terminal-3 power transfer with comparable errors.The steady-state offset reflects unequal line resistances and DC voltage drops present under either controller.Source: §V · p. 8, Figure 9 · p. 9
- Islanded operating points follow the predicted frequency–power characteristic, and DC-voltage points remain within the analytical envelope.DMFD remains stable when Terminal 2 disconnects from its local grid, whereas the GFL baseline loses stability.Source: §V · p. 8, Figure 11 · p. 9, Figure 10 · p. 9
- DMFD maintains stable operation and post-fault recovery on a weak AC tie, while the GFL baseline becomes unstable under the same disturbance.The Terminal-4 tie has SCR = 2; the terminal is preloaded at 0.75 pu.Source: §V · pp. 8–9
VI. CONCLUSION
The conclusion establishes that DMFD grid forming at every AC terminal is compatible with a unique operating point in a meshed MVDC network, without a dedicated DC-voltage regulator. Its current-feedback channel contributes damping, and simulations show stable islanding and weak-tie fault ride-through while retaining conventional DC-droop behavior.
VI. CONCLUSION
- AC synchronization under DMFD closes an effective DC droop, so the connected mesh has a unique operating point without direct DC-voltage or current regulation.An AC-frequency bias at one terminal becomes a bounded, linear DC-network quantity that can be budgeted in voltage and current envelopes.Source: §VI · p. 9
- The same mechanism permits islanding without reconfiguration, with island frequency fixed by local power balance and the DC excursion predictable from island demand.The frequency bias also redistributes power across the mesh, a coupling absent in GFL-based MTDC schemes.Source: §VI · pp. 9–10
- Removing DMFD current feedback leaves an undamped oscillatory mode and renders the system marginally stable.The conclusion identifies sensitivity to nonuniform droop and line asymmetry, and comparison with voltage-only DC droop, as future work.Source: §VI · p. 10
- Weak-tie fault ride-through and islanding stability are obtained without giving up conventional MTDC steady-state DC-droop behavior.The conclusion frames this compatibility as structural rather than dependent on tuning.Source: §VI · pp. 9–10